Heat exchanger area and LMTD calculator

Enter the inlet and outlet temperatures, the heat duty and the overall heat transfer coefficient. The calculator gives the LMTD and the area you need.

°C
°C
°C
°C
kW
W/m²K

Typical: water to water in plate exchangers 3,000 to 7,000; shell and tube water to water 800 to 1,500; gas to gas 10 to 50.

1 for pure counterflow or parallel flow. Shell and tube exchangers with several tube passes usually have 0.8 to 0.95.

Required area
– m²
LMTD
– K
ΔT at end 1
– K
ΔT at end 2
– K

    How the area is calculated

    A heat exchanger transfers heat in proportion to its area, the heat transfer coefficient and the temperature difference between the streams. Rearranged for the area:

    A = Q ÷ (U · F · LMTD)

    LMTD = (ΔT1 − ΔT2) ÷ ln(ΔT1 ÷ ΔT2)

    For counterflow, ΔT1 = Thot,in − Tcold,out and ΔT2 = Thot,out − Tcold,in. For parallel flow both streams enter at the same end, so ΔT1 = Thot,in − Tcold,in and ΔT2 = Thot,out − Tcold,out.

    Worked example

    Oil cools from 120 °C to 70 °C while water heats from 20 °C to 60 °C, in counterflow. The end differences are 60 K and 50 K, so the LMTD is 54.8 K. For a duty of 150 kW and U = 800 W/m²K the exchanger needs 150,000 ÷ (800 × 54.8) = 3.42 m². In parallel flow the same temperatures give an LMTD of only 39.1 K and need 4.80 m².

    Typical U-values

    Exchanger and fluidsU (W/m²K)
    Plate, water to water3,000 – 7,000
    Shell and tube, water to water800 – 1,500
    Shell and tube, steam to water1,500 – 4,000
    Shell and tube, oil to water100 – 400
    Air-cooled finned tube, water to air25 – 50
    Gas to gas10 – 50

    Ranges for first estimates. The real value depends on velocities, fouling and materials and comes from the exchanger supplier.

    The correction factor F

    The LMTD formula is exact only for pure counterflow and pure parallel flow. Shell and tube exchangers with several tube passes and cross-flow exchangers sit in between. Their effective temperature difference is LMTD × F, with F read from charts for the exchanger type. If F drops below about 0.8, the design is inefficient; use more shells in series or a different exchanger type.

    Questions and answers

    What is LMTD?

    The log mean temperature difference is the average temperature difference that drives heat transfer along a heat exchanger. Because the difference changes along the length, a simple average would overstate it; the logarithmic mean gives the correct value.

    Why is counterflow better than parallel flow?

    In counterflow the streams move in opposite directions, so the temperature difference stays more even along the exchanger. This gives a higher LMTD and lets the cold outlet get hotter than the hot outlet, which is impossible in parallel flow.

    What is a temperature cross?

    When the cold outlet is hotter than the hot outlet, the temperatures cross. Pure counterflow handles this; single-shell multi-pass designs cannot, and their correction factor F drops sharply. Then you need more shells in series or a plate exchanger.

    Where do I get the U-value?

    From the exchanger data sheet, or from typical ranges for your fluids and exchanger type as a first estimate. Fouling lowers U over time, so designers add a fouling allowance.